|
AN205
Comparison
of Time Domain Reflectometry vs. Frequency Domain Reflectometry (TDR
vs. FDR)
Written
by
Bill Ashley
for
AEA
Technology Inc.
Abstract
A
few manufacturers of test equipment tout the technology of an FDR as
being superior to a TDR. One
has gone so far as to publish brochures that compare their $6000
FDR’s performance against a bare bones $300 TDR (without
mentioning that the TDR they comparing against is a low end unit).
You can get a quality TDR for under $1500 that outperforms an
FDR in a number of categories. The
FDR manufacturers’ statement that “The FDR measures at
frequency and therefore is better than a TDR” is true under
special circumstances. This
paper compares and contrasts the FDR and TDR technologies and
explains the advantages of each type of instrument. In particular,
the AEA Technology’s VIA EchoTM 2500 FDR’s readings
are compared with an AEA 20/20 TDRTM (step TDR).
The
TDR takes measurements in the time domain and is independent of
frequency. Here’s
another way to think of it…the step TDR makes its measurements
over all frequencies, while the FDR concentrates its measurement
over a selected sweep of frequencies. This paper explains the
conditions when an FDR measurement “at frequency” has an
advantage over a TDR. However,
the FDR process to convert return loss information into a
reflectometry measurement uses an inverse FFT.
This return loss/inverse FFT process introduces major
limitations to the displayed information.
For a fraction of the cost of an FDR, a step TDR displays the
information about your cable in much greater detail.
Introduction
One
FDR manufacturer makes claims about how poorly TDRs perform (the
“FDR is better than a TDR” myth).
It is not fair to use the limitations of a low end $300 TDR
and infer that all TDRs have these limitations.
A quality TDR costing under $1500 can see the defects that
the $6000 FDR shows (plus a few things the FDR can’t see).
Here
are some of the claims made about TDRs.
Only ONE of these claims is true when a quality TDR like the
AEA 20/20 TDR is used in a comparison against the FDR.
We will discuss each of these issues in detail in the next
section.
|
Claim
Statement
|
Claim
Accuracy
|
|
A
TDR only measures open or short faults
|
FALSE
|
|
A
TDR operates at DC
|
FALSE
|
|
A
TDR has poor sensitivity
|
FALSE
|
|
A
TDR cannot monitor small performance changes
|
FALSE
|
|
A
TDR cannot find a corroded junction
|
FALSE
|
|
A
TDR cannot support a preventative maintenance program
|
FALSE
|
|
A
TDR cannot measure return loss
|
FALSE
|
|
A
TDR uses a different measurement technique than FDRs
|
TRU
|
Not
only does the 20/20 TDR find virtually all defects found by FDRs,
but the 20/20 TDR has several advantages not found in FDRs:
|
Advantages
of a TDR over an FDR
|
|
The
20/20 TDR differentiates series faults from shunt faults
|
|
The
20/20 TDR displays accurate loop resistance vs. distance
|
|
The
20/20 TDR allows the user to zoom in on a section of the cable
|
|
The
20/20 TDR does NOT use odd ball step increments on the
distance scale
|
|
The
20/20 TDR does NOT require that you know the length a cable in
advance
|
|
The
20/20 TDR does NOT give false distances caused by aliasing
|
|
The
20/20 TDR costs significantly less
|
Note
that the limitations of the FDR cannot be overcome by buying a more
expensive unit; the FDR limitations are inherent to the FDR
technique.
The
FDR does have some advantages over the TDR.
If measurements are required in any of the following
situations, then the FDR would be a better choice, even with the
loss of the TDR advantages listed in the table above.
|
Advantages
of an FDR over a TDR:
|
|
FDR
measurements can see through narrow band inline frequency
selective components (diplexers) and show information on the
far side.
|
|
FDR’s
operate with higher levels of interference.
|
If
the cable under test contains frequency selective components
(duplexers, diplexers, cavities etc.), or if the antenna at the end
of the cable receives signals greater than -10dBm, then the FDR
performs better. The
20/20 TDR has filters that allow the unit to operate with some
interferers, such as an ADSL modem, broadband signals, or 60 cycle
noise etc, but these filters do not effectively reject strong
broadcast signals.
In
the absence of the above situations, the 20/20 TDR provides more
information about the cable than any FDR.
Discussion
Measurement
at Frequency
We
start with the
sales
pitch about measuring “at frequency”.
This sounds very compelling, why would this not be an
advantage? Major
limitations to this advantage appear under real world conditions.
Most antennae will have moderate to high Q bandwidths (narrow
BWs) and are fed by a feedline.
It will be explained in detail later that an FDR must sweep a
wide band of frequencies to prevent alias distortion.
The feedline, not the load, dominates the
required sweep settings. This can lead to either of two problems:
1.
The vast majority of
the FDR sweep lies outside the antenna’s bandwidth, i.e. not “at
frequency” (wide sweep width).
2.
The cable information
gets scrunched up on the left side of the plot (narrow sweep width).
In
the first case, most of the FDR sweep is not at frequency, and the
readings obtained at some arbitrary frequency give very similar
results as those measured “at frequency”.
In the second case, the feedline may only extend for 10% of
the plot width, reducing detail to marginal levels.
Virtually all cable faults can be detected whether the
measurement is done at one frequency or another. This happens
because cable faults rarely affect only a specific bandwidth but
rather cause broadband degradations.
Examples here show various FDR measurements on an antenna
with feedline. The first
chart shows a good cable/load combination at three different
frequency sweeps, the second chart shows a faulty cable/load with
the same three sweeps. The
three FDR sweeps used are:
A)
Sweep centered on the
antenna resonant frequency
B)
Sweep not centered
on, but including the antenna resonant frequency
C)
Sweep entirely
excludes the antenna resonant frequency
All
traces show a connector at 11 feet 3 inches with approximately 24 dB
of return loss. The peak
at 31 ½ feet is the antenna/end of feedline.
All events after 31 ½ feet are aliasing artifacts and should
be ignored. Note that 4
traces (no load or not on frequency) have about 4dB of return loss at
the end of the feedline. The
other two sweeps have lower return losses of 6 and 13 dB as the sweep
has more energy at the antenna frequency.
The differences overall are not huge, it would be difficult to
say with certainty if the reading indicates the presence of an antenna
or not unless there were previous readings to reference.
Another
plot compares the FDR reading (left axis) with a step TDR reading (AEA
20/20 TDR on the right axis) using the same feedline and antenna.
The TDR shows 1.4 ohms of impedance change at the connector (10
foot 2 inches). The TDR
also shows the cable ending at 31 ½ feet.
The first few feet of the TDR trace show a soft rise due the
waveform characteristics. Returning
to the connector at 10 foot 2 inches, the TDR trace shows that the
cable Z0 before the connector is 49.9 ohms but after the connector the
cable Z0 is 51.3 ohms. Even though both sections of the feedline are
supposed to be 50 ohms (RG213/U cable), the TDR shows the actual Z0s
on each section of the feedline. These
impedances were confirmed using a laboratory grade vector impedance
meter.
A
lossy (resistive) connector could also produce this type of plot. By
inspection and measuring at the connector, one can determine which
condition exists. Another
method would be to look at the cable from the other end; a resistive
connection will always raise the impedance reading of the cable after
the connector. If the
connector is good, the cables will read the same impedances as before
(but in opposite order). The
FDR does not give any additional information by measuring the cable
from the other end.
While
the FDR and TDR plots show similar results (connector and antenna
distances) for the same feedline, the TDR plot also shows mismatch
direction and absolute impedance level.
Signal
Energy
In
order to make the TDR seem inferior, the competition shows a graph
comparing the spectral distribution of the FDR vs. TDR.
The sin(x)/x curve for the TDR shows that a pulse type TDR, not
a step TDR, was used for their graph.
Our graph compares the step
TDR vs. an FDR. Since
the step TDR processes reflected voltage while the FDR processes
reflected power (return loss) comparision of the TDR vs. FDR signal power
spectrums becomes misleading. To better reflect how the two units
detect, process, and display the signal, the plot below shows the FDR
frequency sweep power distribution vs. the voltage distribution of the
TDR step waveform. The FDR
sweep divides the power evenly amongst the 250, 500, or 1000 points of
its sweep; we show the 250 points case in this plot (1000 points would
be 30 dB down). This plot
compares two units with the same output level (0dBm) with the FDR set
to a 700 MHz center frequency and a 600 MHz wide sweep. Note
that the FDR signal has limited frequency range, while the TDR has a
steady drop in amplitude as frequency increases.
A step TDR actually covers a wider range of frequencies than an
FDR, but the FDR can concentrate its energy in a narrower band.
This difference will give the FDR an advantage when a frequency
selective component or interfering signal is on the line being
measured.
Water
Faults
Some
faults are caused when water leaks into the coaxial feedline.
The FDR and TDR plots for a damp cable are shown here.
Each graph compares the faulty cable plot with the same cable
prior to the fault. With a
TDR, the water fault has its distinct signature, a drop in impedance
from the start of the wet cable to the end of the cable or end of the
water. If there is
standing water inside the cable, the plot will drop to zero and the
end of the cable will not be detected.
Note that the plot shown here shows that the cable is longer
with the water fault, this is because the VF in the wet section has
dropped and slowed the pulse down.
Distance measurements in and beyond the wet section are
distorted and can not be relied upon (for either TDR or FDR).
Finding the length of the wet section requires a measurement
from each end of the cable, then subtract these readings from the
total length. The FDR plot
shows the water fault, but one really can’t be sure its a fault or
the end of the cable unless they know that the cable is longer than
the 12 foot reading shown on the graph.
Once the FDR user has determined there is a fault, they have no
indication as to the nature of the fault until the visual examination
discovers it. Since the
water entry point could be a long distance beyond the detected fault
distance indicated by the TDR/FDR, being able to clearly distinguish a
water fault from other fault types gives the TDR user an important
advantage.

Displayed
Information
While
both types of reflectometers show the distance to a fault, that is
where the similarity ends. The units of display on a step TDR are
Ohms, not the dB scale that FDRs use.
A step TDR displays conductor/connector resistances as they
accumulate over the length of the cable.
The step TDR also displays the measured Z0 of the
cable. An FDR shows
neither of these important characteristics.
The
example plot here shows a 120 foot length of quality, low loss cable
followed by a 90 foot length of low quality cable.
Note how the TDR shows the Z0 for each section, plus the flat
slope of the first section indicates low loss coax while the steep
slope of the second section indicates a lossier coax.
There is no information on the FDR trace to indicate the Z0 or
the quality of each section, only the distances to the connection and
to the end are clearly shown.
Another
quirk of FDR’s cause oddball distance increments on the horizontal
scale. The finite
synthesizer step size (typically 10 KHz or worse in FDRs) combined
with the cable velocity factor and the sweep bandwidth to produce an
inflexible and usually irregular step size (e.g.
9.7 inches per step). The
FDR will label the horizontal axis with a round number, but this
merely masks the irregularity of the actual distance increments.
The 20/20 TDR uses an internal resolution much finer than the
displayed resolution, so the TDR sweeps cables with any velocity
factor using even, customary step sizes (e.g. 1.0 inch per step, with
<0.2% full scale error).
Since
the return loss information, used by the FDR, is scalar, the user does
not know the direction of the mismatches, only their magnitudes.
Step TDRs display the mismatch direction, thus you can
distinguish a high Z fault from a low Z fault.
This additional information, provided by the step TDR, improves
fault analysis, because a series loss shows differently than a shunt
loss. On the other hand,
an FDR does not distinguish between these conditions.
Thus
the impedance display of a step TDR shows far more information than
the return loss display of an FDR.
Preventative
Maintenance
The AEA 20/20 TDR includes the TDR PC VisionTM software
that allows one to expand on the TDR’s capabilities.
Data can be saved in the unit and transferred to the desktop PC
in your office (or to a laptop PC anywhere).
Data can be stored on the hard disk to create historical files.
By comparing readings of a particular site from one time to the
next, preventative maintenance can be practiced by replacing/repairing
only the cables that have degraded, while leaving the non-degraded
cables intact. Data in TDR
PC Vision can be exported to spreadsheets so that customized
calculations, comparisons, or plots can be performed.
There are no licenses required to use TDR PC VisionTM which
enables coworkers and customers to examine and use any TDR files you
send to them.
Measurement
Artifacts
The
inverse FFT process used by an FDR possesses an artifact known as
“aliasing”. It is
beyond the scope of this paper to provide a tutorial on aliasing;
there are plenty of papers written on the subject.
The result of aliasing is that you must choose your FDR sweep
to measure the entire
length of the cable. In practice you will have to set the sweep to
measure beyond
the end of the cable to be certain that there is no aliasing.
Improperly setting the FDR frequency sweep causes aliasing,
which results in incorrect
distance information. This requirement that the entire cable be swept,
along with the finite number of display points, combine to limit your
resolution on longer feedlines. On the other hand, quality step TDRs
do not alias so these limitations do not apply. A step TDR can look at
any segment of the cable (i.e. you can zoom in on a fault).
Displaying a portion of the cable with the step TDR does not
introduce any false readings. Thus
the cable length and number of displayed points do not limit the
displayed resolution. The
20/20 TDR can always display its finest resolution over some segment
of the cable (sometimes over the entire length). For the 20/20 TDR
this corresponds to 1 inch or 2cm for any 160 foot (25 meter) segment.
If
the TDR or FDR does not exactly match the Z0 of the cable
under test, the reflectometer sends secondary and tertiary reflections
down the cable. These
extra reflections cause “ghosts” of the cable beyond the actual
end of the cable. The
20/20 TDR always displays these ghosts at distances beyond the end of
the cable, while the inherent aliasing of the FDR may cause these
ghosts to appear at distances before the end of the cable, displaying
false events.
Performance
Summary
|
Measurement
property
|
20/20
TDR (step TDR)
|
FDR
|
Quality
Pulse TDR
|
Cheap
TDR
|
|
Distance
to Fault
|
Y
|
Y
|
Y
|
Note
1
|
|
Z
sensitivity
|
0.1
ohms
|
0.1
ohms, Note 2
|
N/A
|
N/A
|
|
Z0
|
Y
|
No,
Note 3
|
N
|
N
|
|
Conductor
resistance
|
Y
|
N
|
N
|
N
|
|
Series
vs. shunt fault
|
Y
|
N
|
Y
|
N
|
|
Display
Cable Ohms
|
Y
|
N
|
N
|
N
|
|
Display
Cable Return Loss
|
Y
|
Y
|
N
|
N
|
|
Note
4
|
|
Display
Cable SWR
|
Y
Note
4
|
Y
|
N
|
N
|
|
Zoom
in to any cable segment
|
Y
|
N
|
Y
|
N
|
|
Control
of distance increment (resolution)
|
Y
|
N
|
Y
|
N
|
|
Note
5
|
|
Measure
delay match between cable pairs
|
Y
|
N
|
Y
|
N
|
|
Immune
to false readings due to aliasing
|
Y
|
N
|
Y
|
Y
|
|
Cost
|
$$$
|
$$$$$$$$$$$$
|
$$$
|
$
|
|
Remove
test lead from display
|
Y
|
Y
|
Y
|
N
|
|
Measure
at Frequency
|
N
|
Y,
Note 6
|
N
|
N
|
|
Measure
cable with Diplexer in line
|
N
|
Y
|
N
|
N
|
|
Higher
interference immunity
|
N
|
Y
|
N
|
N
|
Notes:
- Can
only measure faults that are opens or shorts.
- This
0.1 ohms is implied when directivity is better than 55dB.
- The
FDR can express how close the cable Z is to the ideal Z0,
but can not distinguish lower Z from higher Z.
This cable Z to ideal Z0 ratio is expressed in
terms of return loss or SWR.
- Converting
from ohms to return loss or SWR is just a calculation.
See Application Note http://www.aeatechnology.com/html/AN_Html/AN103.htm
for details of these calculations. The 20/20 TDR always displays
the cable impedance but the PC Vision software can display the
cable in any of these formats.
- Distance
resolution is some odd value that results from the combination of
sweep width (forced by feedline length) and velocity factor.
- The
length of the feedline limits the frequency sweep settings and the
sweep may exceed the frequency band of interest.
Conclusion
What
is the advantage of using an FDR instead of a TDR?
Let’s use a Swiss army knife analogy.
If a saw blade is added to the knife, it has increased utility.
The saw blade could save your hide in a pinch.
However, if you want to cut a bolt, a hacksaw would be a better
choice. It would cut cleaner and faster, with fewer scraped knuckles
to boot. To extend this
analogy to reflectometers: The FDR increases the utility of a network
analyzer, and may come in handy should the user not want to climb down
the tower to grab the TDR from the truck.
However, if measuring cable is a routine requirement, a quality
step TDR, such as the AEA Technology’s 20/20 TDR, will often be a
more useful tool than an FDR. It
should become standard equipment on the technician’s tool belt.
How
to chose between an FDR or a TDR? Use
the performance comparison chart above to decide which type of
reflectometer meets the necessary requirements. A
few cases need an FDR instead of the 20/20 TDR.
Unless you do testing through diplexer type components or are
in high interference environments, an FDR will probably not be
required
Reflectometry
may be accomplished using two methods, FDR and TDR.
Low quality TDRs are worse than FDRs, but a quality step TDR
will outperform any FDR on the market in all but a few categories.
If one measures cable regularly, they should add the 20/20 TDR
to their tool belt and experience the increased productivity that will
be obtained from the ability to distinguish series faults from shunt
faults, easy to track step size, and alias free readings.
|